Explore our new Cybersecurity Terms Glossary, explained by our experts.
Cybersecurity Terms Glossary
IEC 61850 is the international standard for communication in electrical substations, defining a common data model for protection and control devices and three very different message types that run over Ethernet.

What Is IEC 61850?
Before IEC 61850, every substation was a translation exercise. Protection relays from one manufacturer, a control system from another, and a remote terminal unit in the middle converting between proprietary protocols, with the engineering effort repeated at every site. IEC 61850 replaced that with a standard data model and a standard set of services, so that a circuit breaker is described the same way regardless of who built the relay controlling it.
It is now the backbone of substation automation worldwide, and in Great Britain it underpins the transmission and distribution substation refurbishment programmes that are replacing electromechanical and early digital equipment.
Everything is modelled as logical nodes with standardised names. A circuit breaker is XCBR, a measurement unit is MMXU, a distance protection function is PDIS. Those nodes hold data objects with defined semantics, so an engineer or a tool knows that a given attribute is a breaker position and not a manufacturer-specific integer.
Alongside the model is the Substation Configuration Language, an XML format describing the devices, their capabilities, and the data flows between them. A substation’s SCD file is the authoritative description of the installation, and for a security team it is simultaneously the best asset inventory available and a document that should not be left on a contractor’s laptop, since it describes the entire protection scheme.
Security differs sharply between them. MMS can be protected conventionally. GOOSE and Sampled Values cannot, because their timing budgets leave no room for cryptographic processing in a conventional implementation, and because they are publish-subscribe with no concept of a trusted sender. A device that can place frames on the station bus can publish GOOSE claiming to be any publisher, and subscribers that accept a higher state number will act on it. Researchers have demonstrated trip commands injected this way, and the malware described under Industroyer included a module that spoke IEC 61850 natively, enumerating devices and changing breaker states without touching an operator workstation.
Security for the IEC 61850 family is specified separately in IEC 62351. The relevant parts are 62351-3, which applies TLS to the TCP profiles including MMS; 62351-4, which adds application-level security; 62351-6, which defines authentication for GOOSE and Sampled Values, using message authentication codes designed to fit the latency budget; and 62351-9, which handles key management, the part that makes or breaks any of it in a thousand-substation estate.
Adoption is uneven. TLS on MMS is achievable today. Authenticated GOOSE requires device support, careful performance validation, and a key distribution mechanism that must work in substations with intermittent connectivity. Most utilities therefore rely on architecture: the station bus and process bus are physically separate networks within a locked building, with no path from anywhere else, and the conduit to the control centre is tightly filtered. That is a sound position provided the engineering access path is held to the same standard, which is where assessments usually find the gap.
In the United Kingdom, substation operators are regulated under the NIS Regulations 2018 with Ofgem as competent authority, assessed against the NCSC Cyber Assessment Framework, so the integrity of protection and control communications is a regulated outcome. At Privia Security, we assess substation automation architectures through our OT-SCADA Penetration Test.
GOOSE is the Generic Object Oriented Substation Event message, a multicast Ethernet frame used for fast peer-to-peer signalling between protection devices, with a performance target of a few milliseconds. It has no IP layer, no connection, and no sender authentication in the base standard, and its timing budget leaves little room for conventional cryptography, so most protection against spoofing comes from network isolation.
Not inherently, but it changes the exposure. Older schemes used dedicated copper and proprietary serial links that required physical presence. IEC 61850 puts protection signalling on Ethernet with a published, well-documented model, which makes an attacker who reaches the station bus far more capable. The standard also makes the installation self-describing, which cuts both ways.
The Substation Configuration Description is the XML file defining every device, data flow, and GOOSE subscription in a substation. For engineers it is the single source of truth; for a security team it is both an excellent asset inventory and a highly sensitive document, because it describes the entire protection scheme. It belongs under version control with restricted access.
No standard is mandated by name. The NIS Regulations require appropriate and proportionate measures, assessed against outcomes in the NCSC Cyber Assessment Framework. IEC 62351, alongside strong network separation and access control, is one credible way of demonstrating the communications integrity outcome, and regulators respond well to a documented adoption plan tied to the asset replacement cycle.
You May Be Interested In These
We use a few cookies that are needed to make this website work, and they are always on. We would also like to set analytics cookies, to see which pages are useful; functional cookies, so that our live chat works; and advertising cookies, to measure our campaigns. We will not set any of those until you say yes, and you can change your mind at any time from the Cookie Settings link in the footer.
Choose the cookies you are happy for us to use. Strictly necessary cookies are always on; everything else is off until you turn it on.
These cookies keep the website working: they hold your security checks, your form submissions and the choice you make here. The site cannot run without them, so they are always on.
These let our live chat open and remember your conversation, and let the newsletter sign-up work. Switch them off and the chat window will not appear.
These tell us which pages are read and how people find us, so that we can improve the site. The reports are about groups of visitors, never about you personally.
These let us measure our advertising and show you our adverts on other websites, such as LinkedIn, Google and Meta. Switch them off and you will still see adverts, but they will be less relevant.