Explore our new Cybersecurity Terms Glossary, explained by our experts.
Cybersecurity Terms Glossary
HART carries digital data over the analogue 4-20 mA current loops that connect process instruments, and WirelessHART is its mesh radio successor with mandatory AES-128 encryption.

What Are HART and WirelessHART?
Walk into any process plant and the signal from a pressure transmitter to the control system is still, very often, a current between 4 and 20 milliamps on a pair of wires. HART, the Highway Addressable Remote Transducer protocol, is the clever trick that put digital communication on top of that without disturbing it: a low-amplitude frequency-shift-keyed signal is superimposed on the loop current, with 1,200 Hz and 2,200 Hz tones representing bits. The analogue measurement continues unaffected, and alongside it the device can report diagnostics, secondary variables, calibration data, and its own identity.
The practical consequence is that millions of installed instruments are addressable computers rather than passive sensors, and most plants have never thought of them that way.
Configuration is done either from an engineering workstation running asset management software, through a multiplexer attached to the marshalling cabinets, or with a handheld communicator clipped directly onto the terminals.
There is no authentication. A device accepts commands from whoever is on the loop, protected in most installations by nothing more than a configurable write-protect setting and a lock code that is frequently left at default. Physical access to the terminals, a marshalling cabinet, or a HART multiplexer is therefore equivalent to configuration access to every instrument behind it.
What makes this more serious than it first appears is the nature of the manipulation available. Changing the range of a transmitter does not break anything visibly; it changes the relationship between the current the control system reads and the physical quantity it represents. The loop still carries a plausible value, the operator graphic still shows a number in the normal band, and the process is quietly running somewhere other than where the control room believes. Safety instrumented functions that take their measurement from a HART-capable transmitter deserve particular attention for exactly this reason, which is why they are commonly specified with write protection enabled in hardware.
The other exposure is upward. HART multiplexers and asset management servers sit on the plant network, speak to a distributed control system or a historian, and are usually Windows applications with the same patching difficulties as everything else in the control room.
WirelessHART, standardised internationally as IEC 62591, was published in 2007 and was the first open wireless standard for process automation. It uses 2.4 GHz radios based on IEEE 802.15.4, arranged as a self-organising mesh where every field device also routes for its neighbours, with time-synchronised channel hopping to coexist with Wi-Fi and resist interference.
Security is mandatory rather than optional, which is unusual in this field:
The weaknesses are operational. Many deployments use a single common join key across the whole plant, because provisioning per-device keys is fiddly, and that key is often left in the configuration tool or printed in commissioning documentation. Key rotation is rarely performed. And jamming the 2.4 GHz band remains possible, which is why WirelessHART is specified for monitoring and diagnostics rather than closed-loop control.
Treat the gateway as a zone boundary: it translates between the radio mesh and Modbus TCP, EtherNet/IP, or OPC UA, which makes it a conduit in IEC 62443 terms and the right place for filtering and logging. Enable write protection on transmitters and set lock codes away from defaults. Control physical access to marshalling and junction boxes with the same seriousness as a comms cabinet. Keep an inventory of instruments with their configured ranges, and compare it periodically against what the devices actually report, because that comparison is the detection mechanism for the quiet manipulation described above. Provision unique join keys, record them properly, and rotate them when contractors change.
At Privia Security, we assess field instrumentation layers and their gateways within our OT-SCADA Penetration Test.
It is a risk proportional to physical access. Anyone who reaches the terminals, a marshalling cabinet, or a HART multiplexer can reconfigure instruments, and the manipulation can be subtle enough that the control system continues to display plausible values. Where multiplexers and asset management servers connect to the plant network, that physical requirement disappears for anyone who reaches those systems.
Yes. AES-128 in CCM mode is mandatory at both the link and network layers, providing confidentiality and integrity, with join keys, a network key, and per-session keys managed by a Security Manager. Every message carries a message integrity code. The practical weaknesses are key management rather than cryptography: shared join keys, keys left in configuration tools, and keys never rotated.
It is overwhelmingly used for monitoring, diagnostics, and non-critical measurement. The mesh introduces latency and jitter that make it unsuitable for fast closed-loop control, and the 2.4 GHz band can be jammed or congested. Where wireless is used in a control function at all, it is with a designed safe behaviour on communication loss and a documented process hazard assessment.
Keep a baseline inventory of every HART device with its configured range, units, damping, and failure mode, and periodically compare it against what the devices report through the asset management system. Enable configuration change logging where the platform supports it, and treat an unexplained range change on a transmitter feeding a safety or custody function as an incident rather than a maintenance note.
You May Be Interested In These
We use a few cookies that are needed to make this website work, and they are always on. We would also like to set analytics cookies, to see which pages are useful; functional cookies, so that our live chat works; and advertising cookies, to measure our campaigns. We will not set any of those until you say yes, and you can change your mind at any time from the Cookie Settings link in the footer.
Choose the cookies you are happy for us to use. Strictly necessary cookies are always on; everything else is off until you turn it on.
These cookies keep the website working: they hold your security checks, your form submissions and the choice you make here. The site cannot run without them, so they are always on.
These let our live chat open and remember your conversation, and let the newsletter sign-up work. Switch them off and the chat window will not appear.
These tell us which pages are read and how people find us, so that we can improve the site. The reports are about groups of visitors, never about you personally.
These let us measure our advertising and show you our adverts on other websites, such as LinkedIn, Google and Meta. Switch them off and you will still see adverts, but they will be less relevant.